Energy Valve
A control valve with a built-in ultrasonic flow meter and supply-side temperature and pressure sensors that measures and manages cooling energy at each cabinet or CDU.
- Family
- Direct Liquid Cooling & Secondary Loop Support
- Make
- Taloar
- Lead time
- 45 days
- Projects
- On request
How it works
The Taloar IDCV100C-S4 is a DN20 to DN50 tri-clamp valve (ISO 2852) for cold-plate liquid cooling. The valve sits on the return line and a temperature and pressure sensor on the supply line, so it measures flow, temperature difference, pressure, differential pressure and energy. It can hold a minimum temperature difference, applies a differential pressure function so every cabinet gets enough flow, and keeps its position or moves to a preset opening when the signal is lost. Settings are made over Bluetooth or remotely, and data goes out over Modbus RTU/TCP, MQTT or analog signals.
Role in the system
- 1.Flow control per cabinet with ±2% flow measurement
- 2.Temperature difference limiting for chiller-plant efficiency
- 3.Energy, flow, temperature and pressure data to the BMS or platform
Supplied to
Project references for this item are shared on request with your quotation.
Include in your quotation request
- Valve size (DN20 / 25 / 32 / 40 / 50) and design flow
- Signal (Modbus RTU/TCP, MQTT, 0(2)–10 V, 0(4)–20 mA)
- Fluid (water, ethylene glycol, propylene glycol, deionized water)
- Installation (integrated or split, primary or secondary side of the CDU)
- 24 VDC isolated power supply
- Quantity
This checklist is filled into the quotation form for you. Leave blank what you don't know yet.
Open the pre-filled quotation form